asokatechnologies@gmail.com 09347143789/09949240245

Search This Blog

Friday 15 May 2015

Fault Current Interruption by the Dynamic Voltage Restorer

ABSTRACT
This paper introduces and evaluates an auxiliary control strategy for downstream fault current interruption in a radial distribution line by means of a dynamic voltage restorer (DVR). The proposed controller supplements the voltage-sag compensation control of the DVR. It does not require phase-locked loop and independently controls the magnitude and phase angle of the injected voltage for each phase. Fast least error squares digital filters are used to estimate the magnitude and phase of the measured voltages and effectively reduce the impacts of noise, harmonics, and disturbances on the estimated phasor parameters, and this enables effective fault current interrupting even under arcing fault conditions. The results of the simulation studies performed in the PSCAD/EMTDC software environment indicate that the proposed control scheme: 1) can limit the fault current to less than the nominal load current and restore the point of common coupling voltage within 10 ms; 2) can interrupt the fault current in less than two cycles; 3) limits the dc-link voltage rise and, thus, has no restrictions on the duration of fault current interruption; 4) performs satisfactorily even under arcing fault conditions; and 5) can interrupt the fault current under low dc-link voltage conditions.

KEYWORDS
             1.  Digital filters
      2.  Dynamic Voltage Restorer (DVR),
3.      Fault current interrupting,

4.      Multiloop control.

SCHEMATIC DIAGRAM
                                                           Fig. 1. Schematic diagram of a DVR with a line-side harmonic filter                                           

                                                            Fig. 2. Single-line diagram of the system used for simulation studies.

SIMULATION RESULTS
               Fig. 3. (a) Voltages at Bus3. (b) Fault currents, during downstream three-phase fault when the DVR is inactive (bypassed).                                       
        Fig. 4. (a) Voltages at Bus3, (b) Fault currents, during downstream phase –tophase fault when the DVR is inactive (bypassed).
 Fig.5 . (a) Injected voltages. (b) Source voltages. (c) Load voltages. (d) Line currents. (e) DC-link voltage, during the three-phase downstream fault.
Fig. 6. (a) Voltages at Bus3. (b) Fault currents, during the downstream single phase-to-ground arcing fault when the DVR is inactive (bypassed).

CONCLUSION
This paper introduces an auxiliary control mechanism to enable the DVR to interrupt downstream fault currents in a radial distribution feeder. This control function is an addition to the voltage-sag compensation control of the DVR. The performance of the proposed controller, under different fault scenarios, including arcing fault conditions, is investigated based on time-domain simulation studies in the PSCAD/EMTDC environment. The study results conclude that:
• the proposed multiloop control system provides a desirable transient response and steady-state performance and effectively damps the potential resonant oscillations caused by the DVR LC harmonic filter;
• the proposed control system detects and effectively interrupts the various downstream fault currents within two cycles (of 50 Hz);
• the proposed fault current interruption strategy limits the DVR dc-link voltage rise, caused by active power absorption, to less than 15% and enables the DVR to restore the PCC voltage without interruption; in addition, it interrupts the downstream fault currents even under low dc-link voltage conditions.
• the proposed control system also performs satisfactorily under downstream arcing fault conditions.

REFERENCES
[1] N. G. Hingorani, “Introducing custom power,” IEEE Spectr., vol. 32, no. 6, pp. 41–48, Jun. 1995.
[2] J. G. Nielsen, F. Blaabjerg, and N. Mohan, “Control strategies for dynamic voltage restorer compensating voltage sags with phase jump,” in Proc. IEEE APEC’, 2001, pp. 1267–1273.
[3] G. J. Li, X. P. Zhang, S. S. Choi, T. T. Lie, and Y. Z. Sun, “Control strategy for dynamic voltage restorers to achieve minimum power injection without introducing sudden phase shift,” Inst. Eng. Technol. Gen. Transm. Distrib., vol. 1, no. 5, pp. 847–853, 2007.
[4] S. S. Choi, B. H. Li, and D. M. Vilathgamuwa, “Design and analysis of the inverter-side filter used in the dynamic voltage restorer,” IEEE Trans. Power Del., vol. 17, no. 3, pp. 857–864, Jul. 2002.
[5] B. H. Li, S. S. Choi, and D. M. Vilathgamuwa, “Design considerations on the line-side filter used in the dynamic voltage restorer,” Proc. Inst. Elect. Eng., Gen. Transm. Distrib., vol. 148, no. 1, pp. 1–7, Jan. 2001.