ABSTRACT:
Grid
connected photovoltaic (PV) system encounters different types of abnormalities
during grid faults; the grid side inverter is subjected to three serious
problems which are excessive DC link voltage, high AC currents and loss of
grid-voltage synchronization. This high DC link voltage may damage the
inverter. Also, the voltage sags will force the PV system to be disconnected
from the grid according to grid code. This paper presents a novel control
strategy of the two-stage three-phase PV system to improve the Low-Voltage
Ride-Through (LVRT) capability according to the grid connection requirement.
The non-linear control technique using Improved Particle Swarm Optimization (IPSO)
of a PV system connected to the grid through an isolated high frequency DCeDC
full bridge converter and a three-phase three level neutral point clamped DC-AC
converter (3LNPC2) with output power control under severe faults of grid voltage.
The paper, also discusses the transient behavior and the performance limit for
LVRT by using a DC-Chopper circuit. The model has been implemented in
MATLAB/SIMULINK. The proposed control succeeded to track MPP, achieved LVRT
requirements and improving the quality of DC link voltage. The paper show
KEYWORDS:
1.
Particle swarm optimization
2.
Maximum power point tracking
3.
PV system
4.
High frequency isolated converter
5.
Low voltage ride through
6.
Grid
SOFTWARE: MATLAB/SIMULINK
BLOCK DIAGRAM:
Fig.
1. Block diagram of the PV system connected to the grid.
Fig.
2. PV module characteristics (a) Current-voltage characteristics (b)
power-voltage characteristics.
Fig.
3. Behavior of PV array under normal condition using IPSO.
Fig.
4. DC-link voltage under normal condition using IPSO.
Fig.
5. Behavior of PV array under normal condition using IC.
Fig.
6. DC-link voltage under normal condition using IC.
Fig.
7. Behavior of grid connected inverter system under normal operation.
Fig.
8. The grid voltage fault.
Fig.
9. Behavior of PV array under fault condition.
Fig.
10. DC-link voltage under fault condition.
Fig.
11. Behavior of grid connected inverter system under fault condition.
Fig.
12. Behavior of PV array with LVRT capability.
Fig.
13. DC-link voltage during a grid fault with LVRT capability.
Fig.
14. Behavior of grid connected inverter system with LVRT capability.
CONCLUSION:
Based on the existing grid requirements, this paper
discussed the potential of a two-stage three-phase grid-connected PV system operating
in grid fault condition. The power control method proposed in this paper is
effective when the system is under grid fault operation mode. It can be
concluded that the future three-phase grid-connected PV systems are ready to be
more active and more “smart” in the regulation of power grid.
Non-linear robust control technique using IPSO
control is implemented for MPPT of 100.7 kW PV system connected to the grid.
Complete control of both active and reactive powers is implemented using
Matlab/Simulink with complete simulation under severe faults of grid voltage.
The results show superior behavior of the IPSO; it has a faster dynamic
response and better steady-state performance than the traditional algorithm; IC
method, thus improving the efficiency of the photovoltaic power generation
system. The use of full bridge single phase inverter with a high frequency
transformer which combines the advantages of 60 Hz technology and transformer-
less inverter technology, achieved MPPT requirements with IPSO. Also, this
system overcomes the drawbacks of DC-chopper parameters design.
Two loops of control for the utility-connected 3LNPC2
are implemented which improve the performance of inverter and reduces the
harmonics in output voltage. This control, also, increases the power injected
to the grid and consequently increases the total efficiency of the system. The
results show that the DC chopper circuit is capable of reducing the DC-link
voltage below threshold values during the fault and protect it from failure or
damage. The IPSO is capable of tracking MPP with LVRT capability included.
An anti-wind up conditioned strategy is used in
order to improve the quality on the DC link voltage during and after the grid fault.
It succeeds to stop accumulation of the integral part during fault, which helps
system to follow up pre-faults values rapidly after clearing the fault.
Finally, simulated results have demonstrated the feasibility of the IPSO
algorithm and capability of MPPT in grid-connected PV systems with LVRT
enhancement.
REFERENCES:
[1] Ramdan B.A. Koad, Ahmed. F. Zobaa,
Comparison between the conventional methods and PSO based MPPT algorithm for
photovoltaic systems, Int. J. Electr. Electron. Sci. Eng. 8 (2014) 619e624.
[2] Ali Reza Reisi, Mohammad Hassan Moradi,
Shahriar Jamas, Classification and comparison of maximum power point tracking
techniques for photovoltaic system: a review, Renew. Sustain. Energy Rev. 19
(2013) 433e443.
[3] N.H. Saad, A.A. Sattar, A.M. Mansour,
Artificial neural controller for maximum power point tracking of photovoltaic
system, in: MEPCON’2006 Conference, II, El-MINIA, Egypt, 2006, pp. 562e567.
[4] Raal Mandour I. Elamvazuthi, Optimization
of maximum power point tracking (MPPT) of photovoltaic system using artificial
intelligence (AI) algorithms, J. Emerg. Trends Comput. Information Sci. 4
(2013) 662e669.
[5] Saeedeh Ahmadi, Shirzad Abdi, Maximum
power point tracking of photovoltaic systems using PSO algorithm under
partially shaded conditions, in: The 2nd Cired Regional Conference, Tehran,
Iran, 14, 2014, pp. 1e7.